Sizing a DIN Rail Power Supply: The 30 Percent Rule and Why It Exists
The nameplate on a DIN rail supply is measured at 25 degrees C with free convection. Inside a sealed cabinet in a workshop in August, neither condition holds.
Every supply datasheet carries a derating curve: full rated current up to some temperature (often 45 or 50 degrees C), then a linear fall to about 50-60 percent at 70 degrees C. If you need 5A in a cabinet that reaches 60 degrees, a 5A unit is already at or past its limit.
Hence the 30 percent rule: size the supply so your continuous load is no more than about 70 percent of the rated current at your actual cabinet temperature. The headroom absorbs inrush from contactors and motor drivers, gives the supply room to run cooler (which roughly doubles capacitor life), and covers the load growth that happens when someone adds a relay or a sensor later.
Inrush is the part people forget. Capacitive loads at switch-on can draw several times the steady current for a few milliseconds. A supply sized exactly to the steady load will either current-limit (dropping the output, which can reset your PLC) or trip into hiccup mode.
Efficiency matters more than it looks. A 90 percent efficient 240W supply dissipates about 27W as heat inside the cabinet. A cheaper 85 percent unit dissipates 42W — nearly 15W more, which you then pay to remove with a fan or a larger enclosure.
Finally, check the protection set: short circuit, overvoltage, overload. A supply with hiccup-mode short-circuit protection recovers automatically when the fault clears; one with latching protection needs a power cycle, which on a remote site means a service call.