Solenoid Valves: 5/2, 3/2 and 2/2 — What the Numbers Decide
The notation is positions/ways: a 5/2 valve has five ports and two positions. Once that is clear, the selection becomes mechanical.
A 5/2 valve is the standard choice for a double-acting cylinder. Two output ports drive the piston in each direction, one supply, two exhausts. It is what you want when the actuator must be powered both ways.
A 3/2 valve suits a single-acting cylinder or any application where the actuator is spring-returned. Three ports, two positions: supply, output, exhaust.
A 2/2 valve is an on/off in-line valve — used for isolating a line, not for driving an actuator. This is the configuration in most small water and air shutoff applications.
The second decision is normally-open versus normally-closed, which describes the state with no power. For anything safety-related, normally-closed is usually correct: loss of power removes the supply rather than applying it.
The third is single versus double solenoid. A single-solenoid valve with spring return goes to a defined state when power is lost. A double-solenoid valve holds its last position, which is what you want for a cylinder that must stay extended through a power interruption — and exactly what you do not want for anything that should fail safe.
Flow capacity is the fourth, and it is where undersizing shows up. Port size is a rough indicator but the flow coefficient (Cv or Kv) is the real number. An undersized valve makes the cylinder slow and can cause erratic motion at low speed, which gets misdiagnosed as a mechanical problem.
Finally, check the medium. A valve rated for air is not automatically rated for water or oil — the seal material differs. Using an air valve on a water line usually works for a while and then leaks.